Touch Support DF-CH1 Datacenter Specs

Touch Support's global footprint now includes the DuPont Fabros CH1 datacenter facility in Elk Grove Village, IL. The DF-CH1 datacenter provides ServerCentral the flexibility to facilitate high-density private cabinets and cages. Touch Support's diverse-path fiber ring provides reliable and redundant connections to our backbone network.
General Information:
| Facility Provider: |
DuPont Fabros Technology, Inc |
| Address: |
2200 Busse Rd., Elk Grove Village, IL 60007 |
| NPA-NXX: |
847-787 |
| Location Orientation: |
8 miles from O'Hare airport, 27 miles from Midway airport, near I-90 expressway |
| Commissoned: |
2008 |
| Building Area: |
485,000(sq ft) gross - 221,000(sq ft) raised floor |
| Parking: |
518 spots onsite |
Computer Room Specifications (Per Room)
| Raised Floor Space: |
10,000 square feet (approx.) |
| Colocation Space: |
6,200 square feet |
| Electrical Capacity: |
1,300kW of critical load |
| Power Density: |
210 watts/sqft, up to 12kW/cabinet supported |
| Floor Load Capacity: |
450psf |
| Building Type: |
Single story, raised floor |
| Raised Floor Height: |
42" |
| Fire Suppression: |
Laser-based Very Early Smoke Detection (VESDA) Pre-action zoned dry-pipe system |
| Redundancy: |
Minimum N+1 on all systems |
Facility Information:
| Primary Voltage: |
34.5kV |
| # of Utility Feeders: |
2 |
| # of Power Transformers: |
8 |
| UPS: |
16 - 1,300kW rotary powered systems |
| Standby Power: |
16 - 2,250kW diesel generator systems |
| Fuel Capacity: |
100,000 gallons of diesel |
| Cooling System: |
8 - 1,150 ton centrifugal chillers |
| Thermal Energy Storage: |
500,000 gallons of chilled water |
| Data Pathways: |
2 diverse fiber vaults for redundant carrier points of entry |
| Roof Access: |
Available |
| Loading Dock: |
4 enclosed and heated bays, hydraulic dock levelers |
| Office Space: |
Up to 40,000 square feet of contiguous space available in attached building |
Security:
| Building and Perimeter: |
Bullet-resistant protection at security check-in and level III walls and doors |
| Security Staff: |
24/7/365 staffing with at least 2 officers |
| Access Control: |
Dual-factor authentication system (keycard + biometrics) |
| Alarm System: |
Yes |
| CCTV: |
Camera surveillance archived onsite and offsite |